Which of the following step does NOT hold true for the steps involved in Newton-Raphson method of load flow study?

This question was previously asked in
SJVNL ET Electrical 2019 Official Paper
View all SJVN Executive Trainee Papers >
  1. Use the estimated |V|(0) and δ(0) to formulate the Jacobian matrix J(0)
  2. Choose initial values of the voltage magnitude |V|(0) of all np load buses and n-1 angles δ(0) of the voltages of all the buses except the slack bus
  3. Use the estimated |V|(0) and δ(0) to calculate a total np number of injected reactive power \(\rm Q_{calc}^{(0)}\) and equal number of reactive power mismatch ΔQ(0)
  4. Use the estimated |V|(0) and δ(0) to calculate a total n number of injected real power \(\rm P_{calc}^{(0)}\) and equal number of real power mismatch ΔP(0)

Answer (Detailed Solution Below)

Option 4 : Use the estimated |V|(0) and δ(0) to calculate a total n number of injected real power \(\rm P_{calc}^{(0)}\) and equal number of real power mismatch ΔP(0)
Free
SJVN ET General Awareness Mock Test
0.8 K Users
20 Questions 20 Marks 12 Mins

Detailed Solution

Download Solution PDF

Explanation:

Newton-Raphson Method in Load Flow Study

The Newton-Raphson method is a widely used numerical technique for solving non-linear algebraic equations, and it plays a crucial role in load flow studies of power systems. The method is iterative and converges quickly under normal operating conditions, making it a preferred choice for solving power flow problems in large and complex networks.

Correct Option Analysis:

The correct option is:

Option 4: Use the estimated |V|(0) and δ(0) to calculate a total n number of injected real power \(\rm P_{calc}^{(0)}\) and equal number of real power mismatch ΔP(0).

This step does NOT hold true in the context of the Newton-Raphson method for load flow study. Let us analyze this:

  • The Newton-Raphson method does not involve the calculation of the total number of injected real power (\(\rm P_{calc}\)) for all buses, as it primarily focuses on load buses (PQ buses) and the phase angles of the generator buses (PV buses).
  • In a typical load flow analysis, the slack bus is used to balance the total system power, and its voltage magnitude and angle are predetermined. Therefore, the real power mismatch ΔP(0) is not calculated for all n buses.
  • Instead, the method focuses on calculating mismatches only for load buses (PQ buses) and generator buses (PV buses) where power injections are not fixed.
  • Hence, the calculation of real power mismatches (ΔP) for all buses, including the slack bus, is incorrect and does not align with the Newton-Raphson method.

Steps in the Newton-Raphson Method:

To clarify, let us review the key steps involved in the Newton-Raphson method for load flow analysis:

  1. Initialization: Choose initial values for the voltage magnitudes |V|(0) for all load buses (PQ buses) and angles δ(0) for all buses except the slack bus. These are typically set to flat start values, e.g., |V| = 1 p.u. and δ = 0°.
  2. Formulate the Jacobian Matrix: Use the initial estimates of |V|(0) and δ(0) to compute the Jacobian matrix J(0), which represents the partial derivatives of the power mismatches with respect to voltage magnitudes and angles.
  3. Calculate Mismatches: Using the initial estimates, calculate the real power mismatch ΔP and reactive power mismatch ΔQ for PQ and PV buses based on the difference between specified power and calculated power (\(\rm P_{spec} - P_{calc}\) and \(\rm Q_{spec} - Q_{calc}\)).
  4. Solve for Corrections: Solve the linearized set of equations ΔX = J⁻¹ × ΔP/Q to determine the corrections to voltage magnitudes and angles.
  5. Update Estimates: Update the voltage magnitudes and angles using the corrections, i.e., |V|(k+1) = |V|(k) + Δ|V| and δ(k+1) = δ(k) + Δδ.
  6. Convergence Check: Repeat steps 2–5 until the mismatches ΔP and ΔQ are within a predefined tolerance.

As seen above, the focus is on mismatches for PQ and PV buses, and not for all n buses, which validates why Option 4 is incorrect.

Additional Information

To further understand, let’s evaluate the other options:

Option 1: Use the estimated |V|(0) and δ(0) to formulate the Jacobian matrix J(0).

This is a correct step in the Newton-Raphson method. The Jacobian matrix plays a critical role as it contains the partial derivatives of the power mismatches with respect to voltage magnitudes and angles. It is formulated using the initial estimates of |V| and δ.

Option 2: Choose initial values of the voltage magnitude |V|(0) of all np load buses and n-1 angles δ(0) of the voltages of all the buses except the slack bus.

This is also a correct step. Initial values are required to begin the iterative process, and they are typically chosen as flat start values (|V| = 1 p.u., δ = 0°) for simplicity.

Option 3: Use the estimated |V|(0) and δ(0) to calculate a total np number of injected reactive power \(\rm Q_{calc}^{(0)}\) and equal number of reactive power mismatch ΔQ(0).

This is another correct step. For load buses (PQ buses), the reactive power mismatches ΔQ are calculated based on the difference between specified and calculated reactive power (\(\rm Q_{spec} - Q_{calc}\)).

Conclusion:

The Newton-Raphson method is an effective and widely used numerical technique for load flow analysis in power systems. Understanding the correct sequence of steps is crucial to its successful implementation. Option 4 is incorrect as it misrepresents the scope of the calculations involved, specifically suggesting the calculation of real power mismatches for all buses, which is not performed in this method. Instead, the focus is on PQ and PV buses, with the slack bus serving as the reference point for balancing power in the system.

Latest SJVN Executive Trainee Updates

Last updated on Jul 15, 2025

-> SJVN Executive Trainee Written Exam date is out, The computer based exam will be held on 10th, 14th August 2025.

->SJVN Executive Trainee recruitment 2025 application form has been released. Applicants can apply for the SJVN recruitment 2025 Executive Trainee till May 18.

->SJVN Limited has announced the recruitment notification for the position of Executive Trainee 2025.

->A total of 114 vacancies are available for the SJVN Executive Trainee Recruitment across various disciplines such as Civil, Mechanical, Electrical, Environment, Electronics & Communication, and more.

->The selection process of SJVN Executive Trainee recruitment 2025, as per the previous notification, includes a Computer-Based Test, Group Discussion, and Personal Interview.

->Once selected, candidates will be required to sign a service agreement bond of Rs. 10,00,000/- (Rs. 7,50,000/- for SC/ST/PWD candidates), committing to complete the prescribed training and serve the company for a minimum of 3 years.

->Candidates must refer to the SJVN Executive Trainee Previous Year Papers and boost their preparation for the exam.

More Newton Raphson Method Questions

Get Free Access Now
Hot Links: teen patti king teen patti pro teen patti master king teen patti vungo