Question
Download Solution PDFIn an air-conditioning plant, air enters the cooling coil at 27°C. The coil surface temperature is -5°C. If the bypass factor of the unit is 0.4, the air will leave the coil at:
Answer (Detailed Solution Below)
Detailed Solution
Download Solution PDFConcept:
Bypass Factor represents the fractional part of total inlet air which is not in contact with the coil.
Bypass factor of a cooling coil is given by
\(BPF = \frac{{{T_{outlet}} - {T_{coil}}}}{{{T_{inlet}} - {T_{coil}}}}\)
Calculation:
Given, BPF = 0.4, T1 = 27°C, Tc = -5°C,
\(0.4 = \frac{{{T_2} - \left( { - 5} \right)}}{{27 - \left( { - 5} \right)}}\)
T2 + 5 = 12.8°C
⇒ T2 = 7.8°CLast updated on Jul 2, 2025